Abstract:
Studies of seismic performance of brick build
ings have revealed their inadequacy to resist earth
quake shocks due to their heavy weight, poor tensile
strength, low shearing resistance, lack of proper
bonding between the shear walls and the cross-walls
and poor workmanship. Systematic dynamic studies do
not appear to have been carried out for investigating
their realistic seismic capabilities. The strengthen
ing methods as recommended in some of the earthquake
regulations of the countries are meant for conventional
brick buildings to improve their performance with
little increase in the overall cost. But a dynamic
evaluation of the specification is still wanting. The
aim of this thesis is to fill this gap to some extent
as well as to examine a new possibility of saving such
buildings from the damaging influence of earthquake on
the principle of vibration isolation. The following
studies are made:
1. Seismic Response Analysis of Conventional
Buildings
A typical multistoreyed brick building is
chosen here for seismic response analysis. A number
of variables representing the physical properties of
the structural system, namely, number of storeys from
one to four, wall thickness in various storeys from 1
(iii)
to li brick thick and damping from 5 to 15$ of
critical value are considered. Shear beam type multidegrees
freedom system is taken to represent these
buildings mathematically in which the masses of the
floors end walls are assumed as lumped at the floor
levels, the floors are assumed as rigid diaphragms and
the 'Pier Method* is to use to derive the storey
stiffness. The restoring force versus lateral deflec
tion characteristics are assumed to be linear in each
storey. Both shearing and bending deformations are
considered to take place in the piers. Two accelero
grams are used for computing dynamic response of the
buildings : (a) Longitudinal component of Koyna earth
quake of December 11, 1967 recorded close to the
epicentre of the shock and having high acceleration
pulses and high frequency contents and (b) North-
South component of El Centro shock of May 18, 1940
recorded at about 50 km from the epicentre and having
relatively lower acceleration peaks and frequency con
tents. Runge-Kutta fourth order method is used for
computing the seismic response. Overturning and tor
sional effects have been included in the determination
of timewise net stresses in the piers and their capa
bilities have been examined for resisting earthquake
shock. From this study the critical sections for
providing reinforcing have been identified and the
minimum amount of necessary steel has been estimated.
(iv)
2. Brick Buildings with Sliding Joint
at Plinth Level
To investigate the ground motion isolation
feasibility, a new system is considered in which a
clear smoothened surface is created at plinth level just
above the damp-proof course and the superstructure simply
rests at this level and is free to slide except for the
frictional resistance. Pilot tests carried out on 2/4
scale models showed very large reduction in the roof
acceleration as compared with conventional fixed base
case under given shake table motion indicating a definite
possibility of- earthquake isolation. The seismic res
ponse of one storey sliding type buildings is worked
out through a two-mass mathematical model treating the
frictional resistance as rigid plastic. The various
parameters involved in the analysis are: time period,
roof-base mass ratio, viscous damping and coefficient
of friction. The seismic response of the system is
computed using the same acceleograms and the same
numerical techniques as for the conventional system.
This study leads us to a concept of 'frictional response
spectra* in which the spectral quantities of a sliding
mass-spring-dashpot system are plotted against the
undamped natural period for various coefficiants of
friction and mass ratios. These spectra clearly show
the reduction of response of sliding system as compared
with the conventional buildings.
(v)
3. Large Model Shake Table Tests on
Conventional and Sliding Buildings
Eight half scale single storeyed brick
building models are tested under base shocks so as to
study their behaviour upto ultimate failure when cons
tructed with different strengthening arrangements or
sliding base arrangement. Their relative competence
to withstand severe shocks is throughly examined. The
outside dimensions of these models are 2.17 m x 1.75 m
in plan and 1.60 m high above the plinth level with a
7.5 cm reinforced concrete slab roof. The tests were
performed on a specially made railway wagon shake table
facility in group of four models at a time. The eight
models were of the following types?
(a) Conventional Fixed Base Types - One each,
unstrengthened, in mud and cement mortars; one unstren
gthened in cement mortar but with lintel band; One
strengthened in cement mortar with lintel band and
vertical steel at corners and jambs; and another simi
larly strengthened in cement mortar but with plinth
band in addition.
(b) Sliding Types - One each in mud and cement
mortars having lintel band. These tests show that
unstrengthened brick buildings of conventional cons
truction are not only weak but inadequate in energy
absorption and that models with horizontal ring beam
at lintel level and vertical reinforcement at critical
(vi)
sections achieve strength and toughness both. The
models with sliding permitted at base, again show a
significant reduction in response and adequate behaviour
upto very high base accelerations. As such, sliding
arrangement shows great promise for adoption in actual
building construction as a measure of earthquake safety.
The following main conclusions are drawn:
Once a brick building cracks, its stifiness,
strength as well as damage threshold acceleration go on
reducing and at a faster rate as the extent of damage
increases. Reinforcing the brickwork at critical
sections both in vertical and horizontal directions is
a must for achieving adequate plateau of strength and
ductility. The critical sections are identified and
an estimate of required steel given for moderate and
severe seismic zones. A sliding joint created at
plinth level between foundation and superstructure
could be used as an effective means of isolating the
base motion.