DSpace Repository

PC BASED PROTECTIVE RELAYING FOR TRANSFORMERS

Show simple item record

dc.contributor.author Kumar, Ajay
dc.date.accessioned 2014-12-08T07:18:51Z
dc.date.available 2014-12-08T07:18:51Z
dc.date.issued 1999
dc.identifier M.Tech en_US
dc.identifier.uri http://hdl.handle.net/123456789/13604
dc.guide Gupta, Bharat
dc.description.abstract The present, work aims at development of a percentage biased harmonic restrained- differential- protection using PC for a single phase power transformer. - The -protective Scheme, differential protection of power transformers consists in converting the primary and secondary line currents to a common base using appropriately connected CTs- of Suitable ratios and comparing these currents. During, normal • operating conditions, the difference between._these currents is small, resulting from normal magnetizing current. and small ' CT errors. This difference during external faults can be. quite -large because of a difference in the dynamic behaviours of CTs on the two sides of the transformer.. On the contrary, during a. winding (internal) fault, the difference current may not be very large.- If only a small portion of the .winding is short circuited. en_US
dc.language.iso en en_US
dc.subject ELECTRICAL ENGINEERING en_US
dc.subject PC BASED PROTECTIVE RELAYING en_US
dc.subject TRANSFORMERS en_US
dc.subject SINGLE PHASE POWER TRANSFORMER en_US
dc.title PC BASED PROTECTIVE RELAYING FOR TRANSFORMERS en_US
dc.type M.Tech Dessertation en_US
dc.accession.number 248323 en_US


Files in this item

This item appears in the following Collection(s)

Show simple item record