Please use this identifier to cite or link to this item: http://localhost:8081/xmlui/handle/123456789/14362
Title: CONDITION MONITORING AND PROTECTION OF TRANSMISSION LINE USING PMU
Authors: Navendu
Keywords: Naive Bayes (NB) Classifier;Transmission Line;Fault Classification
Issue Date: May-2016
Publisher: Department of Electrical Engineering,IITR.
Abstract: Naive Bayes (NB) Classifier has been implemented for fault detection and type of fault classification in transmission line. The Naïve Bayes classifier is based on Bayes conditional probability theorem. Synchronized fault current is taken from two PMU placed at two alternate buses. The magnitude and angle of all the three phase current are considered for fault classification of transmission line. First the line on which fault has occurred has been identified using Naive Bayes classifier. Then type of fault is classified using maximum value of phase current. Since, PMU gives RMS value as output and the faulty phase shows maximum value of RMS current. So the maximum value of each phase current is used in Naïve Bayes classifier for fault classification. Ten different types of fault have been classified. It classifies the fault very accurately. The classifier is very simple to understand and use. It takes very less time for training and testing.
URI: http://hdl.handle.net/123456789/14362
metadata.dc.type: Other
Appears in Collections:DOCTORAL THESES (Electrical Engg)

Files in This Item:
File Description SizeFormat 
G25941-Navendu-D.pdf1.52 MBAdobe PDFView/Open