Please use this identifier to cite or link to this item:
http://localhost:8081/jspui/handle/123456789/13604| Title: | PC BASED PROTECTIVE RELAYING FOR TRANSFORMERS |
| Authors: | Kumar, Ajay |
| Keywords: | ELECTRICAL ENGINEERING;PC BASED PROTECTIVE RELAYING;TRANSFORMERS;SINGLE PHASE POWER TRANSFORMER |
| Issue Date: | 1999 |
| Abstract: | The present, work aims at development of a percentage biased harmonic restrained- differential- protection using PC for a single phase power transformer. - The -protective Scheme, differential protection of power transformers consists in converting the primary and secondary line currents to a common base using appropriately connected CTs- of Suitable ratios and comparing these currents. During, normal • operating conditions, the difference between._these currents is small, resulting from normal magnetizing current. and small ' CT errors. This difference during external faults can be. quite -large because of a difference in the dynamic behaviours of CTs on the two sides of the transformer.. On the contrary, during a. winding (internal) fault, the difference current may not be very large.- If only a small portion of the .winding is short circuited. |
| URI: | http://hdl.handle.net/123456789/13604 |
| Other Identifiers: | M.Tech |
| Research Supervisor/ Guide: | Gupta, Bharat |
| metadata.dc.type: | M.Tech Dessertation |
| Appears in Collections: | MASTERS' THESES (Electrical Engg) |
Files in This Item:
| File | Description | Size | Format | |
|---|---|---|---|---|
| EED 248323.pdf | 1.89 MB | Adobe PDF | View/Open |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.