Please use this identifier to cite or link to this item: http://localhost:8081/xmlui/handle/123456789/13604
Title: PC BASED PROTECTIVE RELAYING FOR TRANSFORMERS
Authors: Kumar, Ajay
Keywords: ELECTRICAL ENGINEERING;PC BASED PROTECTIVE RELAYING;TRANSFORMERS;SINGLE PHASE POWER TRANSFORMER
Issue Date: 1999
Abstract: The present, work aims at development of a percentage biased harmonic restrained- differential- protection using PC for a single phase power transformer. - The -protective Scheme, differential protection of power transformers consists in converting the primary and secondary line currents to a common base using appropriately connected CTs- of Suitable ratios and comparing these currents. During, normal • operating conditions, the difference between._these currents is small, resulting from normal magnetizing current. and small ' CT errors. This difference during external faults can be. quite -large because of a difference in the dynamic behaviours of CTs on the two sides of the transformer.. On the contrary, during a. winding (internal) fault, the difference current may not be very large.- If only a small portion of the .winding is short circuited.
URI: http://hdl.handle.net/123456789/13604
Other Identifiers: M.Tech
Research Supervisor/ Guide: Gupta, Bharat
metadata.dc.type: M.Tech Dessertation
Appears in Collections:MASTERS' THESES (Electrical Engg)

Files in This Item:
File Description SizeFormat 
EED 248323.pdf1.89 MBAdobe PDFView/Open